Isishwankathelo
Khuphela & Inkxaso

Isiguquli seGridi

R3 ubuninzi

100kW-125kW | Isigaba esiThathu, iiMPPT ezili-9

I-PV inverter i-R3 Max series, i-inverter yesigaba esithathu ehambelana nomthamo omkhulu we-PV panels, isetyenziswa ngokubanzi kwiinkqubo ze-PV ezisasazwayo kunye nezityalo zamandla ze-PV ezinkulu. ixhotyiswe ngokhuseleko lwe-IP66 kunye nolawulo lwamandla olusebenzayo. Ixhasa ukusebenza kakuhle okuphezulu, ukuthembeka okuphezulu, kunye nofakelo olulula.

  • 20A

    Max. PV

    igalelo langoku

  • AFCI

    Ukhetho lwe-AFCI & Smart

    Umsebenzi wokubuyisela i-PID

  • IP66

    Uyilo lwangaphandle

Iimpawu zeMveliso
  • Thumela ngaphandle
    Umsebenzi wolawulo lokuthumela ngaphandle uhlanganisiwe
  • 图标-06

    I-150% yePV igalelo eligqithisiweyo kunye ne-110% yokulayishwa kwe-AC

  • 3
    Uhlobo II SPD kuzo zombini DC kunye AC
  • ILogo Simahla Akukho mlinganiselo Ipapashwe ngu- 特征图标-3

    Ukujongwa komtya kunye nexesha elifutshane le-O&M

Uluhlu lweParameter
Umzekelo I-R3-100K I-R3-110K I-R3-125K
Max. I-PV Input Voltage[V] 1100
Max. Igalelo lePV langoku ngeMPPT [A] 32
Inombolo yeMPPT Trackers/No.of Input strings per Tracker 9/2
Max. I-AC Output Apparent Power [VA] 11000 121000 125000
Max.Ubuchule 98.7%

Isiguquli seGridi

100kW-125kW | Isigaba esiThathu, iiMPPT ezili-9

I-PV inverter i-R3 Max series, i-inverter yesigaba esithathu ehambelana nomthamo omkhulu we-PV panels, isetyenziswa ngokubanzi kwiinkqubo ze-PV ezisasazwayo kunye nezityalo zamandla ze-PV ezinkulu. ixhotyiswe ngokhuseleko lwe-IP66 kunye nolawulo lwamandla olusebenzayo. Ixhasa ukusebenza kakuhle okuphezulu, ukuthembeka okuphezulu, kunye nofakelo olulula.

KhuphelaKhuphela Okunye

Ividiyo yeMveliso

Intshayelelo yemveliso
Ukufakwa kwemveliso

FAQs ezinxulumeneyo

  • 1.Kutheni i-"SPI Fault" iboniswa kwi-inverter screen?

    Unobangela wesehlo:

    Isizathu salo siphoso yingxaki yonxibelelwano phakathi kwee-CPU eziphambili kunye neesekondari zebhodi yokulawula inverter.

    Isisombululo:

    (1)Rqalisa i-inverter (kufuneka ukhuphe i-PV, igridi ye-AC, kunye neebhetri kwaye emva koko uyivule kwakhona).

    (2) Ukuba ingxaki iyaqhubeka emva kokuqalisa kwakhona i-inverter, khangela ukuba i-software version yebhodi yokulawula inverter ichanekile. Ukuba akunjalo, zama ukutshisa kwisoftware kwakhona.

    (3) Ukuba ingxaki iyaqhubeka emva kokutshisa isofthiwe, buyisela ibhodi yokulawula.

  • 2.I-inverter ibonisa impazamo yegridi kwaye ibonise umyalezo wempazamo njengempazamo yamandla ombane "iGrid Volt Fault" okanye impazamo yamatyeli "Grid Freq Fault" "Grid Fault"?

    Unobangela wesehlo: 

    Umbane kunye nokuphindaphinda kwegridi yamandla e-AC angaphandle koluhlu oluqhelekileyo.

     

    Isisombululo:

    Ukulinganisa i-voltage kunye nokuphindaphinda kwegridi yamandla e-AC kunye nesixhobo esifanelekileyo se-multimeter, ukuba ayiqhelekanga ngokwenene, linda ukuba igridi yamandla ibuyele kwisiqhelo. Ukuba i-voltage yegridi kunye ne-frequency iyinto eqhelekileyo, oko kuthetha ukuba i-circuit ye-inverter yokufumanisa iphosakele. Xa ujonga, qala uqhawule igalelo le-DC kunye nemveliso ye-AC ye-inverter, kwaye uvumele i-inverter ibe namandla ngaphezu kwe-30min ukuze ubone ukuba isekethe inokubuyisela ngokwayo, ukuba inokubuyisela ngokwayo, ungaqhubeka ukuyisebenzisa, ukuba ayikwazi ukufunyanwa, ungaqhagamshelana.Renacukutshintshwa okanye ukutshintshwa. Ezinye iisekethe ze-inverter, ezifana ne-inverter main board circuit, isekethe yokufumanisa, isekethe yonxibelelwano, i-inverter circuit, kunye nezinye iimpazamo ezithambileyo, zingasetyenziselwa ukuzama le ndlela ingasentla ukubona ukuba ziyakwazi ukuzibuyisela ngokwazo, kwaye emva koko zigqithise okanye zitshintshe ukuba azikwazi ukubuyisela ngokwabo.

  • 3.I-voltage ephumayo egqithisileyo kwicala le-AC, ebangela ukuba i-inverter ivale okanye ikhuphe ngokhuseleko?

    Unobangela wesehlo:

    Ngokukodwa ngenxa yokuba i-impedance yegridi inkulu kakhulu, xa icala lomsebenzisi we-PV lokusetyenziswa kwamandla lincinci kakhulu, ukuhanjiswa kwe-impedance kuphezulu kakhulu, okukhokelela ekubeni icala le-AC inverter ye-voltage ephumayo iphezulu kakhulu!

     

    Isisombululo:

    1 Okukhona ikhebula lijiyile, kokukhona i-impedance isezantsi.

    (2) I-inverter isondele ngokusemandleni kwindawo edibeneyo yegridi, imfutshane ikhebula, i-impedance ephantsi. Ngokomzekelo, thatha i-inverter ye-5kw edibeneyo yegridi njengomzekelo, ubude bekhebula lokuphuma kwe-AC ngaphakathi kwe-50m, ungakhetha indawo ye-cross-sectional ye-2.5mm2 intambo: ubude be-50 - 100m, kufuneka ukhethe indawo ye-cross-sectional ye-4mm2 cable: ubude obukhulu kune-100m, kufuneka ukhethe indawo ye-cross-section2.