Isishwankathelo
Khuphela & Inkxaso

Isiguquli seGridi

R3 Qaphela

6kW / 8kW / 10kW / 12kW | Isigaba esiThathu, i-MPPTS ezi-2

I-RENAC R3 Note Series inverter yenye yezona zinto zikhethwa kakhulu ezifumanekayo kumacandelo okuhlala kunye nezorhwebo ngamandla ayo obugcisa, nto leyo eyenza ukuba ibe yenye yezona ziguquli zivelisa kakhulu kwimarike. Ngobuchule obuphezulu be-98.5%, ukongezwa kobukhulu kunye namandla okulayisha ngaphezulu, i-R3 Note Series imele ukuphucuka okugqwesileyo kushishino lwe-inverter.

  • 16A

    Max. PV

    igalelo langoku

  • AFCI

    Ukhetho lwe-AFCI

    umsebenzi wokukhusela

  • 150%

    I-150% yePV

    igalelo oversizing

Iimpawu zeMveliso
  • Thumela ngaphandle
    Umsebenzi wolawulo lokuthumela ngaphandle uhlanganisiwe
  • 图标-06

    Uluhlu lwamandla ombane olubanzi lweMPPT (140 ~ 1000V)

  • 3
    Uhlobo II SPD kuzo zombini DC kunye AC
  • ILogo Simahla Akukho mlinganiselo Ipapashwe ngu- 特征图标-3
    Uphuculo lwe-firmware ekude kunye nokuseta
Uluhlu lweParameter
Umzekelo I-R3-6K I-R3-8K I-R3-10K I-R3-12K
Max. I-PV Input Voltage[V] 1100
Max. Igalelo lePV langoku [A] 16/16
Inombolo yeMPPT Trackers/No.of Input strings per Tracker 2/1
Max. I-AC Output Apparent Power [VA] 6600 8800 11000 13200
Max.Ubuchule 98.4% 98.5% 98.5% 98.5%

Isiguquli seGridi

6kW / 8kW / 10kW / 12kW | Isigaba esiThathu, i-MPPTS ezi-2

I-RENAC R3 Note Series inverter yenye yezona zinto zikhethwa kakhulu ezifumanekayo kumacandelo okuhlala kunye nezorhwebo ngamandla ayo obugcisa, nto leyo eyenza ukuba ibe yenye yezona ziguquli zivelisa kakhulu kwimarike. Ngobuchule obuphezulu be-98.5%, ukongezwa kobukhulu kunye namandla okulayisha ngaphezulu, i-R3 Note Series imele ukuphucuka okugqwesileyo kushishino lwe-inverter.

KhuphelaKhuphela Okunye

Ividiyo yeMveliso

Intshayelelo yemveliso
Ukufakwa kwemveliso

FAQs ezinxulumeneyo

  • 1.I-inverter ibonisa impazamo yegridi kwaye ibonise umyalezo wempazamo njengempazamo yamandla ombane "iGrid Volt Fault" okanye impazamo yamatyeli "Grid Freq Fault" "Grid Fault"?

    Unobangela wesehlo: 

    Umbane kunye nokuphindaphinda kwegridi yamandla e-AC angaphandle koluhlu oluqhelekileyo.

     

    Isisombululo:

    Ukulinganisa i-voltage kunye nokuphindaphinda kwegridi yamandla e-AC kunye nesixhobo esifanelekileyo se-multimeter, ukuba ayiqhelekanga ngokwenene, linda ukuba igridi yamandla ibuyele kwisiqhelo. Ukuba i-voltage yegridi kunye ne-frequency iyinto eqhelekileyo, oko kuthetha ukuba i-circuit ye-inverter yokufumanisa iphosakele. Xa ujonga, qala uqhawule igalelo le-DC kunye nemveliso ye-AC ye-inverter, kwaye uvumele i-inverter ibe namandla ngaphezu kwe-30min ukuze ubone ukuba isekethe inokubuyisela ngokwayo, ukuba inokubuyisela ngokwayo, ungaqhubeka ukuyisebenzisa, ukuba ayikwazi ukufunyanwa, ungaqhagamshelana.Renacukutshintshwa okanye ukutshintshwa. Ezinye iisekethe ze-inverter, ezifana ne-inverter main board circuit, isekethe yokufumanisa, isekethe yonxibelelwano, i-inverter circuit, kunye nezinye iimpazamo ezithambileyo, zingasetyenziselwa ukuzama le ndlela ingasentla ukubona ukuba ziyakwazi ukuzibuyisela ngokwazo, kwaye emva koko zigqithise okanye zitshintshe ukuba azikwazi ukubuyisela ngokwabo.

     

  • 2.I-voltage ephumayo egqithisileyo kwicala le-AC, ebangela ukuba i-inverter ivale okanye ikhuphe ngokukhusela?

    Unobangela wesehlo:

    Ngokukodwa ngenxa yokuba i-impedance yegridi inkulu kakhulu, xa icala lomsebenzisi we-PV lokusetyenziswa kwamandla lincinci kakhulu, ukuhanjiswa kwe-impedance kuphezulu kakhulu, okukhokelela ekubeni icala le-AC inverter ye-voltage ephumayo iphezulu kakhulu!

     

    Isisombululo:

    1 Okukhona ikhebula lijiyile, kokukhona i-impedance isezantsi.

    (2) I-inverter isondele ngokusemandleni kwindawo edibeneyo yegridi, imfutshane ikhebula, i-impedance ephantsi. Ngokomzekelo, thatha i-inverter ye-5kw edibeneyo yegridi njengomzekelo, ubude bekhebula lokuphuma kwe-AC ngaphakathi kwe-50m, ungakhetha indawo ye-cross-sectional ye-2.5mm2 intambo: ubude be-50 - 100m, kufuneka ukhethe indawo ye-cross-sectional ye-4mm2 cable: ubude obukhulu kune-100m, kufuneka ukhethe indawo ye-cross-section2.

  • 3.DC icala igalelo ombane overvoltage alarm, umyalezo imposiso "PV Overvoltage" eboniswe?

    Unobangela wesehlo:

    Iimodyuli ezininzi kakhulu ziqhagamshelwe kuthotho, okubangela ukuba i-voltage yegalelo kwicala le-DC igqithe ubuninzi bombane osebenzayo we-inverter.

     

    Isisombululo:

    Ngokweempawu zeqondo lokushisa kwiimodyuli ze-PV, iqondo lokushisa eliphantsi le-ambient, i-voltage ephezulu yokuphuma. Kucetyiswa ukuba uqwalasele uluhlu lwe-voltage yomtya ngokwedatha ye-inverter. Kolu luhlu lwamandla ombane, ukusebenza kakuhle kwe-inverter kuphezulu, kwaye i-inverter isenako ukugcina imeko yokuvelisa amandla okuqalisa xa i-irradiance iphantsi ekuseni nangokuhlwa, kwaye ayiyi kubangela ukuba i-voltage ye-DC igqithe umda ophezulu we-inverter voltage, eya kukhokelela kwi-alamu kunye nokucima.