Uhlolojikelele
Landa & Ukusekela

I-Inverter ye-On-Grid

R3 Inothi

6kW / 8kW / 10kW / 12kW | Izigaba ezintathu, 2 MPPTS

I-RENAC R3 Note Series inverter ingenye yezinketho ezingcono kakhulu ezitholakala emkhakheni wezindawo zokuhlala nezohwebo ngamandla ayo obuchwepheshe, okuyenza ibe ngenye yama-inverter akhiqiza kakhulu emakethe. Ngokusebenza kahle okuphezulu okungu-98.5%, amandla athuthukisiwe okulayisha ngokweqile kanye nokulayisha ngokweqile, i-R3 Note Series imele ukuthuthuka okuvelele embonini ye-inverter.

  • 16A

    Ubukhulu. I-PV

    okokufaka kwamanje

  • I-AFCI

    I-AFCI yokuzithandela

    umsebenzi wokuvikela

  • 150%

    I-PV engu-150%.

    ukufaka usayizi oweqile

Izici Zomkhiqizo
  • Thekelisa
    Umsebenzi wokulawula ukuthekelisa uhlanganisiwe
  • 图标-06

    Ibanga lamandla kagesi e-MPPT (140 ~ 1000V)

  • 3
    Thayipha II SPD kukho kokubili i-DC ne-AC
  • 特征图标-3
    Ukuthuthukiswa nokulungiselelwa kwe-firmware yesilawuli kude
Uhlu Lwepharamitha
Imodeli R3-6K R3-8K R3-10K R3-12K
Ubukhulu. I-PV Input Voltage[V] 1100
Ubukhulu. Okokufaka kwe-PV Yamanje [A] 16/16
Inombolo Yama-MPPT Trackers/No.of Input Strings nge-Tracker ngayinye 2/1
Ubukhulu. Amandla abonakalayo okukhipha i-AC [VA] 6600 8800 11000 13200
Ukusebenza kahle okuphezulu 98.4% 98.5% 98.5% 98.5%

I-Inverter ye-On-Grid

6kW / 8kW / 10kW / 12kW | Izigaba ezintathu, 2 MPPTS

I-RENAC R3 Note Series inverter ingenye yezinketho ezingcono kakhulu ezitholakala emkhakheni wezindawo zokuhlala nezohwebo ngamandla ayo obuchwepheshe, okuyenza ibe ngenye yama-inverter akhiqiza kakhulu emakethe. Ngokusebenza kahle okuphezulu okungu-98.5%, amandla athuthukisiwe okulayisha ngokweqile kanye nokulayisha ngokweqile, i-R3 Note Series imele ukuthuthuka okuvelele embonini ye-inverter.

downloadKhipha ku-internet Okuningi

Ividiyo Yomkhiqizo

Isingeniso somkhiqizo
Ukufakwa komkhiqizo

Imibuzo Evame Ukubuzwa Ehlobene

  • 1.I-inverter ibonisa iphutha legridi futhi ibonise umlayezo wephutha njengephutha le-voltage "Iphutha Le-Volt Yegridi" noma iphutha lefrikhwensi "Iphutha Legridi Ye-Freq" "Iphutha Legridi"?

    Imbangela yesigameko: 

    I-voltage nemvamisa yegridi yamandla we-AC ingaphandle kwebanga elijwayelekile.

     

    Isixazululo:

    Linganisa i-voltage nemvamisa yegridi yamandla e-AC ngegiya elifanele le-multimeter, uma ingavamile ngempela, linda igridi yamandla ukuthi ibuyele kokujwayelekile. Uma i-voltage yegridi kanye nemvamisa kujwayelekile, kusho ukuthi isifunda sokutholwa kwe-inverter sinephutha. Uma ubheka, qala unqamule okokufaka kwe-DC kanye nokuphuma kwe-AC kwe-inverter, bese uvumela isiguquli sicime isikhathi esingaphezu kwemizuzu engama-30 ukuze ubone ukuthi isifunda singazimela yini ngokwaso, uma singazilulamela ngokwaso, ungaqhubeka nokusisebenzisa, uma singatholakali, ungathintana.I-Renacukuze kulungiswe noma kushintshwe. Amanye ama-circuits e-inverter, njenge-inverter main board circuit, i-circuit yokuthola, i-circuit yokuxhumana, i-inverter circuit, namanye amaphutha athambile, angasetshenziswa ukuzama le ndlela engenhla ukubona ukuthi angakwazi yini ukuzilulamela ngokwawo, bese ewashintsha kabusha noma ewashintsha uma engakwazi ukuzilulamela ngokwawo.

     

  • 2.I-voltage ephumayo eyeqile ohlangothini lwe-AC, okubangela ukuthi isiguquli sivale noma sinciphise ngokuvikela?

    Imbangela yesigameko:

    Ikakhulukazi ngenxa yokuthi i-impedance yegridi inkulu kakhulu, lapho uhlangothi lomsebenzisi we-PV lokusetshenziswa kwamandla luncane kakhulu, ukudluliswa kwe-impedance kuphezulu kakhulu, okuholela ekutheni uhlangothi lwe-inverter AC lwe-voltage ephumayo luphakame kakhulu!

     

    Isixazululo:

    (1) Khulisa i-diameter yentambo yentambo yokukhiphayo, uma ikhebula lishuba, kwehlisa i-impedance. Ukuqina kwekhebula, i-impedance iyancipha.

    (2) I-inverter iseduze ngangokunokwenzeka endaweni exhunywe kugridi, ikhebula lifushane, i-impedance iphansi. Isibonelo, thatha i-inverter exhunywe kugridi engu-5kw njengesibonelo, ubude bekhebula lokuphuma kwe-AC phakathi kwama-50m, ungakhetha indawo ephambanayo yekhebula elingu-2.5mm2: ubude obungu-50 – 100m, udinga ukukhetha indawo ephambanayo yekhebula engu-4mm2: ubude obungaphezu kuka-100m, udinga ukukhetha indawo ye-cross-section2.

  • 3.DC side okokufaka voltage overvoltage alamu, umyalezo wephutha "PV Overvoltage" ubonisiwe?

    Imbangela yesigameko:

    Amamojula amaningi kakhulu axhunywe ochungechungeni, okubangela i-voltage yokufaka ohlangothini lwe-DC ukuthi idlule umkhawulo ophezulu we-voltage wokusebenza we-inverter.

     

    Isixazululo:

    Ngokusho kwezici zokushisa zamamojula we-PV, ukwehla kwezinga lokushisa elizungezile, ukuphakama kwe-voltage ephumayo. Kunconywa ukuthi ulungiselele ububanzi be-voltage yezintambo ngokuya ngemininingwane yedatha ye-inverter. Kulolu hlu lwe-voltage, ukusebenza kahle kwe-inverter kuphezulu, futhi i-inverter isengakwazi ukugcina isimo sokukhiqiza amandla okuqalisa lapho i-irradiance iphansi ekuseni nakusihlwa, futhi ngeke ibangele i-voltage ye-DC yeqe umkhawulo ongaphezulu we-voltage ye-inverter, okuzoholela ku-alamu nokuvala.